Technical specification
MCB-AC | Wintrip MCB | Wintrip Isolator | ||
Standard conformity | IS/IEC60898-1-2002 | IS/IES60947-3 | ||
Type | B | C | D |
|
Rated current (in) | 6-63A | 0.5-125A | 0.5-63A | 25-125A |
Rated voltage AC (Ue) | 240/415V | 240/415V | ||
Utilization category |
| AC22A | ||
Rated frequency Hz | 50/60Hz | 50Hz | ||
No. of poles (Execution) | 1P,1P+N,2P,3P,3P+n & 4P | 1P,2P,3P, & 4P | ||
Rated short circuit breaking capacity | 10kA | 10kA | 10kA |
|
Rated insulation voltage (Ui) | 660V | 660V | ||
Magnetic release setting | (3-5)In | (5-10)In | (10-20)In |
|
Rated impulse voltage (Uimp) | 4kV | 6kV | ||
Electrical/Mechanical life <32A >32A | 30,000 10,000 | 30,000 10,000 | ||
Ambient temperature | -5°C to +55°C | -5°C to +55°C | ||
Energy limiting class | ELC 3 |
| ||
Mounting | Clip on Din rail (35 mm x 7.5 mm) |
| ||
Line Terminal capacity | 35 mm2 | 35 mm2 | ||
Degree of protection | IP 20 | IP 20 | ||
Resistance to shock | 40mm free fall | 40mm fre fall | ||
Ambient reference temperature | 30°c |
| ||
Installation position | Vertical/Horizontal | Vertical/Horizontal |
1763, 1st Floor, Near HDFC Bank, Gandhi Road, Ahmedabad, Gujarat, 380001, India
Phone :+918037303412